HVAC PIPE DESIGN


PIPE SIZING IN HVAC

PIPE SIZING IN HVAC

Pipe is a conduct or a medium through which any liquid or gas can be passed.

Well similar to duct it is a kind transferring medium through which gas or liquid is been proceeded.

Pipes are very important part in transferring the required liquid or gas to required place with the presence of pressurised pump system which maintains required pressure to flow the liquid to desired point.

Well as we know that either it may be cooling or heating of an area it is not possible and economical to place a different cooling system everywhere hence pipes conduct and takes the responsibility to transfer the liquid or gas medium to required point.

Well the responsibility of the pipe are to supply the cool water and bring the hot water back to the system and repeat this process continuously as an cycle.

AIR CONDITIONING PIPING SYSTEM

AIR CONDITIONING PIPING SYSTEM

In an air conditioning system the pipe which joins compressor ,condenser, expansion valve and evaporator through which refrigerant is passed is called primary refrigerant.

Generally the pipe material used in this air conditioning system are copper.

Well the copper which are used are depending on the amount of capacity and the pressure resisting capacity of an air conditioning system which are made of copper material ,which is soft copper for  up to 2 TR system and above 2 TR hard copper is used.

Well the above system where copper is used are generally for air conditioning system.

CHILLER PIPING SYSTEM

CHILLER PIPING SYSTEM

In chiller system there is additional piping which joins pump, FCU or AHU  and chiller in which chilled water is been supplied is called as secondary chill water piping.

CHILLER CONDENSER PIPING SYSTEM

 CHILLER CONDENSER PIPING SYSTEM

The condenser piping are generally seen in water cool chiller system which connects pumps, cooling tower and shell and tube condenser is called open piping or hot water system.

MATERIALS IN CHILLED WATER PIPING

MATERIALS IN CHILLED WATER PIPING

In chilled water system there are generally two type of material used
Mild steel M.S:
Black steel (low carbon steel)

ARRANGEMENT OF CHILLER PIPING SYSTEM

ARRANGEMENT OF CHILLER PIPING SYSTEM


Well chilled water pipes are generally arranged in two ways:

TWO PIPE DIRECT RETURN SYSTEM

Well have a look at the second arrangement which is called as two pipe direct return system.

From figure you can see the pumps are been connected to the AHU system via pipe connection.

Basically in this system blue coloured chill water is been supplied to the AHU 1  and than to AHU 2 while taking away the used or evaporated water again from AHU 1 and AHU 2 in red colour line.

Hence this system is not hydraulically balanced because the amount of pressure absorb by the AHU 1 is more compared to AHU 2 as we know the flow rate decreases with the coverage length of fluid flowing in the path.

While the extraction of water is also taken place at AHU 1 firstly and than at AHU2 hence this system is not hydraulically balanced.

If the system is not hydraulically balance there are chances of pipe getting leaks and reduce its capacity to hold the pressure of water flowing in it.

Hence to overcome and maintain hydraulically balance system we need to focus on proper systematic arrangement.

TWO PIPE REVERSE SYSTEM

Well have a look at the first arrangement which is called as two pipe reverse return system.

From figure you can see the pumps are been connected to the AHU system via pipe connection.

Basically in this system blue coloured chill water is been supplied to the AHU 2 and than to AHU 1 while taking away the used or evaporated water again from AHU 1 and AHU 2.

Hence the system is hydraulically balanced and there are less chances of getting leakage due to uneven pressure .

This is very important part in arrangement , because it not only hydraulically balance but increases the life of the whole system by contributing to avoid losses of financial bones of a project.

CLASSIFICATION OF PIPE


ACCORDING TO MAUNFACTURING


SEAMLESS PIPES(CONTINUOUS PIPES WITHOUT WELDING JOINTS)
GENERALY USED FOR REFRIGERANT PIPING TO AVOID LEAKAGE AND WITHSTAND HIGH PRESSURE UPTO 40 BARS)

WELDED PIPES (GENERALLY USED FOR CHILLED WATER,HOT WATER,PLUMBING AND FIREFIGHTING)

 ACCORDING TO CLASS


CLASS A OR SCHEDULE 20 OR LIGHT DUTY
CLASS B OR SCHEDULE 40 OR MEDIUM DUTY
CLASS C OR SCHEDULE 60 OR HEAVY DUTY

 ACCORDING TO LOCATION

  ACCORDING TO LOCATION

ROOF ( VELOCITY 10FPS)
RISER(VELOCITY 7 – 10FPS)
FLOOR(VELOCITY 5 – 7 PFS)
MAX VELOCTY 15 FPS
MIN VELOCITY 1.5 FPS

This are the data from carrier handbook data book.

Well maximum velocity which is 15 FPS (feet per second)is to avoid erosion and increase the life of the system.

And minimum velocity in chilled water should not be less than 1.5 FPS(feet per second) in any pipe.

In chilled water pipe sizing before designing it is necessary to know what is the capacity of system.

As we know in normal air conditioning system when heat load is calculated generally the term used is how much ton of capacity ?

 similarly a whole chilled water system also have capacity which is also denoted in terms of tons of capacity or TR.

But to find the pipe size one need to know the GPM of pump system .

So let find it!!!!!!!

CHILLED WATER PIPES(CHILLER TO AHU)

FLOW RATE IN GPM
1GALLONS = 3.78 LTR
GPM=TR X 24/∆T
1 TR =2.4 GPM (IF ∆T IS 10)

CONDENSER COOLING PIPES(CHILLER TO COOLING TOWER)


FLOW RATE IN GPM
1GALLONS = 3.78 LTR
GPM=TR X 30/∆T
1 TR =3 GPM (IF ∆T IS 10)

Well there are two case

If the pipe has to be sized for chilled water system from AHU to chiller than 1 TR =2.4 GPM (IF ∆T IS 10)

If the pipe has to be sized for chilled water system from cooling tower  to chiller than 1 TR =3 GPM (IF ∆T IS 10).

PIPE SIZING METHODS

CONSTANT VELOCITY METHOD
VELOCITY AND FRICTION METHOD

This are the two methods which are generally used in pipe sizing or pipe designing method…

CONSTANT VELOCITY METHOD

As the name suggest in this method the velocity of the fluid  assumed to be constant which have different value for different location …

ROOF ( VELOCITY 10FPS)
RISER(VELOCITY 7 – 10FPS)
FLOOR(VELOCITY 5 – 7 PFS)

So lets take an example so to understand more clearly…
chilled water plant

From the above diagram lets have a look at the chilled water plant

Chiller which has two section (condenser and evaporator).

CHILLER EVAPORATOR is the space which consist of chilled evaporator coils in a shell and tube device which chilled the water by absorbing the heat from it and this chilled water is passed to the AHU or FCU via pump suction and discharge pressure.

CHILLER CONDENSER is the space similar to evaporator space which consist of condenser unit where the refrigerant heat is removed by exchanging the heat in condenser unit via supply of water cycle in connection with pump line to the cooling tower where the hot water is cooled .


So lets take an example of four storey apartment having 900 TR cooling load i.e 540TR per floor

So lets find out the Total GPM required..

1 TR =2.4 GPM (IF ∆T IS 10) assuming std temperature difference

900 x 2.4=2160 GPM

AS we know that as per the location velocity is constant
So lets used pipe sizer …by selecting the following

Pipe class schedule 40
70°F water
2160 GPM,  we get the following data for riser pipe till AHU 1

RISER

1)Q=2160GPM    VMAX=10FPS  V= 8.79FPS(less than 10FPS)  DIA=10`` hl=2.18``/100``

From above figure velocity is 8.79FPS for 10`` diameter if the velocity is more than 10`` it wont be accepted.

Similarly 2)Q=1620GPM    VMAX=10FPS  V=6.59 fps   DIA=10`` hl=1.2``/100``

3)Q=1080GPM    VMAX=10FPS  V=6.93fps   DIA=8`` hl=1.8``/100``

4)Q=540GPM    VMAX=10FPS  V=8.66fps   DIA=5`` hl=4.87``/100``

This is all data for riser pipe size as per the GPM , as the GPM decease the pipe size too decreases.

FLOOR

FLOOR(VELOCITY 5 – 7 PFS)

1)Q=540GPM    VMAX=6FPS  V=6fps   DIA=6`` hl=1.94``/100``

As every floor have same GPM so diameter is also same having velocity lower than 6 FPS.

VELOCITY AND FRICTION METHOD

As we know that in constant velocity method, we avoid the friction consideration, for small size pipe and GPM it is suitable but when it comes to heavy GPM the water tends to corroded the inner pipe resulting in damage and leakage and ultimately break down of the project.

So to avoid it industry follows this process … basically velocity and friction method is combination of both which have certain condition when to used which method.
condition

1.velocity method
if diameter <=2``
velocity<=4fps

2.friction method
if dia >=2``
head loss<=4ft/100ft

well in this method velocity method is used with diameter less than or equal to 2`` when the velocity is less than 4FPS , if its greater than we opt to friction method.

In friction method diameter should be greater than 2`` and  velocity is not the concern here head loss is concerned which must be less than or equal to 4ft/100ft.

So lets take the same example.


VELOCITY AND FRICTION METHOD

RISER



1)Q=2160GPM 
PIPE SIZER
As we can see that with 2`` diameter velocity is 206.52FPS , Which is against the condition1.velocity method =if diameter <=2``,velocity<=4fps

Hence lets opt for friction method

PIPE SIZER


1)Q=2160GPM    DIA=10`` hl=2.18``/100``

This data is accepted according to the  condition of friction method if dia >=2`` head loss<=4ft/100ft

Similarly for others we get the following data

2)Q=1620GPM    DIA=8`` hl=3.9``/100``

3)Q=1080GPM    DIA=8`` hl=1.8``/100``

4)Q=540GPM    DIA=6`` hl=1.94``/100``


FLOOR

4)Q=540GPM    DIA=6`` hl=1.94``/100``

This is all about pipe sizing. Pipe sizing is very important as the economical and safety condition need to followed for optimised design of pipe size.

hope this article helped out to resolve your doubt....



Previous
Next Post »

please don`t enter any spam link in the comment box ConversionConversion EmoticonEmoticon